Edge Solutions

BTM — Boiler Thermocouple Monitoring + ITM Connect

“128 channels of tube-temperature truth in a NEMA4X box.”

BTM — Boiler Thermocouple Monitoring

  • Reads up to 128 thermocouples in one stainless enclosure, every point on the same clock.
  • Supplies every temperature to ITM Connect for trends, alarms and history.
  • Flags a failed thermocouple and leaves it out of the averages, so a bad reading is not mistaken for a temperature.
  • Gives SHOP the tube-metal temperatures it needs to see each tube clear on a start-up.
  • Serves the same values to an Allen-Bradley ControlLogix PLC over EtherNet/IP, as remote I/O.
  • Works for any job that needs thermocouples, on a boiler or off it.
BTM in 41 seconds.

BTM on ITM Connect

BTM began as a boiler product: thermocouples on boiler tubes, read and archived. It is now the wired way to bring a large number of thermocouples into ITM Connect. The thermocouple wires land on terminal blocks in a stainless steel enclosure. An NI CompactRIO controller with thermocouple input modules reads every point continuously, and ITM Connect shows the whole array at once: by bank and leg, against its limits and against its neighbours. One measurement then serves the operator, the plant’s controls and any ITM Connect app that needs temperatures.

BTM on ITM Connect during a boiler start-up: tiles for points in service, the hottest point, points in alarm, the fastest rise, the array average and time since light-off; an array map of 128 thermocouples in eight banks of sixteen legs with two hot legs ringed, one fast riser ringed and one open thermocouple hatched; a table by bank; a trend of one bank since light-off; a list of alarms and events; the status bits sent to the plant; and where the data goes.
BTM on ITM Connect during a boiler start-up. Concept screen with simulated data.
  • Every point, on one time base — one value for each thermocouple every second, with a status for each point.
  • Groups — points grouped by bank, zone or machine, with the average, the highest point and the spread for each group.
  • Limits and alarms — a high limit, a limit on how far a point may sit above its group, and a limit on rate of rise.
  • Thermocouple faults — an open or out-of-range thermocouple is flagged and left out of the averages.
  • Event record — the data around each alarm is kept at full rate for the review.
  • Publishes it to the plant — values and status bits go to the PLC, the DCS and the historian, and the same tags feed SHOP.

At a glance: Up to 128 thermocouples · any standard thermocouple type · NI CompactRIO with 16-channel thermocouple modules · every point each second · stainless NEMA 4X enclosure · EtherNet/IP to ControlLogix · relay or digital outputs can be added for interlocks.

Reading them together is the differentiator. One thermocouple gives a reading. A hundred of them, read at the same moment, give a picture: which leg is hotter than its bank, which one is rising faster than the rest, and which reading cannot be trusted. A limit on each point alone misses most of that. In the example here no tube is above its high limit, yet two legs stand more than 50 °F clear of their bank and one is climbing at 38 °F a minute. Those are the tubes an engineer wants to know about, and they show only when every point is on the same clock and compared with its neighbours.

A trend of one bank of tube thermocouples from light-off: the bank average and the range of its sixteen legs rise together for two hours, then one leg pulls away and ends 56 degrees above the bank average, still below the high limit.
One bank through a start-up: the bank average, the range of its legs, and one leg leaving the rest. Simulated data.

One array. Three views.

The same measurement is shown three ways, because the operator, the engineer and the instrument technician each ask a different question of it.

An array map of 128 thermocouples, eight banks of sixteen legs, coloured from dark blue for cooler to light blue for hotter; two neighbouring legs in the second bank and one leg in the fifth are ringed and show their values, and one cell in the sixth bank is hatched and marked open.

The whole array at one moment

Every thermocouple is a cell, placed by bank and leg and coloured by temperature. A point in alarm is ringed and shows its value; a faulted point is hatched.

Reads — every point at the same instant, beside its neighbours.

Used for — finding the hot leg, the cold leg and the bad thermocouple at a glance.

A table of eight banks with the average, highest and spread of each in degrees Fahrenheit and a status: five banks OK, one with two legs above its average, one with a rate alarm and one with a thermocouple fault.

Each bank against itself

Each bank has an average, a highest point and a spread. A leg that moves away from its bank shows in the spread before it reaches a limit.

Reads — average, highest and spread for every bank, with its status.

Used for — comparing banks through a start-up, and one start-up with the last.

A list of alarms and events from one start-up with time, point, event and detail: a rate-of-rise alarm, two legs above their bank average, an open thermocouple, an earlier rate alarm that cleared, and the start of the record.

What needs attention

Alarms and thermocouple faults are listed as they happen, each with its point, its value and its limit, and the list is kept as the record of the event.

Reads — high, above-group and rate-of-rise alarms, and thermocouple faults.

Used for — the operator’s list during a start-up, and the review afterwards.

Where it is used

BTM was built for boiler tubes. Mills have also used it as remote I/O for thermocouples on other heat sources, and it suits any job with many thermocouples in one place.

Boiler tube metal

Installed — on the thermocouples a superheater or reheater already carries, or on new ones.

Used for — tube-metal temperatures through every start-up, and as the temperature source for SHOP.

Start-up and operating conditions

Installed — on steam tubes or other points that show whether a boiler is ready for its next step.

Used for — confirming start-up conditions, and switching other equipment or interlocks from relay or digital outputs.

Any other thermocouple job

Installed — wherever many thermocouples can be wired to one enclosure.

Used for — remote thermocouple I/O for a ControlLogix PLC, and trends, alarms and history in ITM Connect.

What is in the enclosure

  • Terminal blocks — thermocouple extension wire from the field lands on a panel of thermocouple terminal blocks.
  • Thermocouple modules — NI 9214 modules, 16 channels each, with the cold-junction sensors in the module’s own terminal block. Eight modules read 128 thermocouples.
  • CompactRIO controller — an NI cRIO-9046, or a newer CompactRIO, reads every channel in real time. See the CompactRIO controllers on the Edge Hardware page.
  • ITM Connect — runs on the CompactRIO itself, or on a separate ITM Compute unit that the CompactRIO feeds.
  • Outputs to the plant — EtherNet/IP to a ControlLogix PLC. Relay or digital modules can be added to the CompactRIO for interlocks.
  • Enclosure — stainless steel, NEMA 4X. One enclosure reads up to 128 thermocouples; larger arrays use more than one controller or an expansion chassis.
Drawing of an open stainless steel enclosure: thermocouple wiring enters at the top and lands on two rows of terminal blocks; wires run through a duct to eight thermocouple modules of sixteen channels each beside a CompactRIO controller; a power supply and a ground bar sit below.
Inside a BTM enclosure. Illustration.

Proven on a utility boiler

A paper mill wanted to measure the temperature of steam tubes inside its utility boiler, to make sure start-up conditions were met, and to use temperature changes in normal operation to trigger other equipment and interlocks. ITM built and installed a CompactRIO system that monitors 280 Type K thermocouples.

  • Two CompactRIO controllers and two expansion chassis hold 19 thermocouple modules.
  • Results are shown on a web page, with Modbus, OPC UA, a PI connector and EtherNet/IP available for the plant’s own systems.
  • A real-time application decides whether the temperature conditions are met, and relay modules switch the customer’s equipment and interlocks.
  • Temperatures are logged and the files are transferred to a remote computer.
  • The customer planned to put the same system on more of its utility boilers.
Rows of bent steel boiler tubes stacked side by side.
Boiler tubes

Read the case study →

Wired or wireless?

ITM also makes a Wireless Thermocouple Node. The two do different jobs, and both report to ITM Connect.

BTM, wired

Points — tens to hundreds in one place.

Reading — continuous, every point on one clock.

Wiring — thermocouple wire to one enclosure.

Plant controls — direct to a ControlLogix PLC as remote I/O.

Best for — dense arrays and existing thermocouple wiring.

Wireless Thermocouple Node

Points — a few, spread out.

Reading — battery powered, reports by radio.

Wiring — none.

Plant controls — through ITM Connect.

Best for — points that cable cannot reach economically.

Why it matters

A large recovery boiler has upwards of 250 tube thermocouples to watch during a start-up, in the busiest hours of an outage. Checked one at a time, or scanned slowly, they cannot show an event that lasts a few minutes on one tube. Read together every second, they can. Putting the thermocouple inputs in an enclosure near the measurement, and handing the values to the PLC over EtherNet/IP, also means the plant does not have to add a hundred or more thermocouple inputs to its own control system.

BTM measures, groups, trends and alarms. It does not interpret the temperatures: finding a tube-clearing event is SHOP’s job. Its status bits are advisory and sit beside the plant’s own alarms. Where relay or digital outputs are added for interlocks, what they do is the plant’s decision. A thermocouple in poor condition is reported, not corrected.

A typical deployment

  1. List the points. Agree every thermocouple: tag, location, type, range and limits.
  2. Decide the path. Existing thermocouples and wiring, new thermocouples, or both; where the enclosure goes and how far the wire runs.
  3. Size the system. One enclosure for up to 128 points; more above that. Add relay or digital modules if interlocks are wanted.
  4. Build and test. Assemble the enclosure and test every channel before it ships.
  5. Install. Mount the enclosure, land the thermocouple wires on the terminal blocks, connect power and network.
  6. Check every point. Confirm each reading against its tag and location; correct reversed or open thermocouples.
  7. Connect. Bring the tags into ITM Connect and map them to the PLC, the DCS and the historian.
  8. Set groups and limits. Group the points and enter the limits with the plant.
  9. Hand over. Agree who sees the alarms and who acts on them. Where SHOP is used, it is set up on the same tags.

References: published sources behind this page.

Productized from boiler thermocouple systems ITM has supported for years.